Program Organization

IEC 61131-3 programs are organized in layers. This page explains what each layer does and why the structure exists. For hands-on practice building up these layers step by step, follow the Quick start tutorial.

The Big Picture

An IEC 61131-3 application is built from these building blocks, from innermost to outermost:

CONFIGURATION
└── RESOURCE
    └── TASK
        └── PROGRAM instance
            └── Your control logic

Each layer has a specific purpose:

  • PROGRAM contains the control logic (the code you write).

  • TASK defines how often a program runs.

  • RESOURCE represents a processing unit (a CPU or core).

  • CONFIGURATION ties everything together for a specific hardware setup.

This layered model separates what the program does from how and where it runs. You can change the scan rate or move a program to different hardware without rewriting the logic.

Programs

A PROGRAM is the basic unit of control logic. It declares variables and contains statements that execute on every scan:

PROGRAM main
   VAR
      Counter : INT := 0;
   END_VAR

   Counter := Counter + 1;

END_PROGRAM

Programs are similar to classes in object-oriented languages: they bundle data (variables) with behavior (statements). Unlike classes, programs are not instantiated with new — they are instantiated by a CONFIGURATION (see below).

Variables inside a program retain their values between scans. The Counter variable above will be 1 after the first scan, 2 after the second, and so on.

Functions and Function Blocks

In addition to programs, IEC 61131-3 defines two other kinds of Program Organization Units (POUs):

  • Functions are stateless: they take inputs, compute a result, and return it. They do not retain values between calls. Think of them like pure functions.

  • Function Blocks are stateful: like programs, they have internal variables that persist between calls. Think of them like objects that you can instantiate multiple times.

You use functions and function blocks inside programs to organize your logic into reusable pieces.

Tasks

A TASK defines a scheduling policy. The most common kind is a periodic task that runs at a fixed interval:

TASK plc_task(INTERVAL := T#100ms, PRIORITY := 1);

This says: “run every 100 milliseconds, at priority level 1.”

Tasks control the scan rate. A fast task (T#10ms) reads inputs and writes outputs more frequently, which gives tighter control but uses more CPU. A slow task (T#1s) is gentler on the CPU but less responsive.

You can define multiple tasks with different intervals — for example, a fast task for motion control and a slow task for temperature monitoring.

Resources

A RESOURCE represents a processing unit — typically a CPU or core. It groups tasks and program instances that run on the same hardware:

RESOURCE res ON PLC
   TASK plc_task(INTERVAL := T#100ms, PRIORITY := 1);
   PROGRAM plc_task_instance WITH plc_task : main;
END_RESOURCE

The line PROGRAM plc_task_instance WITH plc_task : main means: “create an instance of the main program, name it plc_task_instance, and run it on plc_task.”

The ON PLC part names the hardware target. In practice, the target name is defined by the runtime environment.

Configurations

A CONFIGURATION is the top-level container. It holds one or more resources and represents a complete deployable unit:

CONFIGURATION config
   RESOURCE res ON PLC
      TASK plc_task(INTERVAL := T#100ms, PRIORITY := 1);
      PROGRAM plc_task_instance WITH plc_task : main;
   END_RESOURCE
END_CONFIGURATION

Every IEC 61131-3 application needs exactly one configuration.

Putting It All Together

Here is a complete, minimal application showing all the layers:

PROGRAM main
   VAR
      Button AT %IX1: BOOL;
      Buzzer AT %QX1: BOOL;
   END_VAR

   Buzzer := NOT Button;

END_PROGRAM

CONFIGURATION config
   RESOURCE res ON PLC
      TASK plc_task(INTERVAL := T#100ms, PRIORITY := 1);
      PROGRAM plc_task_instance WITH plc_task : main;
   END_RESOURCE
END_CONFIGURATION

Reading from the bottom up:

  1. The configuration named config defines one resource.

  2. The resource named res defines one task and one program instance.

  3. The task named plc_task runs every 100 ms.

  4. The program named main reads a button input and controls a buzzer.

For a step-by-step guide to building this up from scratch, see the Quick start tutorial.