Structured Text (ST) is the primary language supported by IronPLC. This page gives you a conceptual overview of the language so you know what to expect when you start writing code. For hands-on practice, follow the Quick start tutorial.

What Structured Text Looks Like

If you have used Pascal, Ada, or even a bit of Python, Structured Text will feel familiar. Here is a small example:

PROGRAM main
   VAR
      Counter : INT := 0;
      Limit : INT := 100;
      Running : BOOL := TRUE;
   END_VAR

   IF Running AND (Counter < Limit) THEN
      Counter := Counter + 1;
   ELSE
      Running := FALSE;
   END_IF;

END_PROGRAM

Some things to notice:

  • Keywords like PROGRAM, VAR, IF, and THEN are uppercase by convention.

  • Variable declarations go inside a VAREND_VAR block at the top.

  • Assignment uses := (not =).

  • Statements end with a semicolon.

  • Blocks are closed with END_PROGRAM, END_IF, and so on rather than curly braces.

Data Types

IEC 61131-3 provides a set of elementary data types:

Type

Size

Description

BOOL

1 bit

Boolean (TRUE or FALSE)

INT

16 bits

Signed integer (-32768 to 32767)

DINT

32 bits

Double integer

REAL

32 bits

Floating-point number

STRING

Variable

Character string

TIME

Duration (for example, T#100ms)

You can also define your own types: enumerations, arrays, structures, and subranges. These are covered in the Data Types.

Control Flow

Structured Text supports the control flow statements you would expect:

IF / ELSIF / ELSE:

IF Temperature > 100.0 THEN
   Alarm := TRUE;
ELSIF Temperature > 80.0 THEN
   Warning := TRUE;
ELSE
   Alarm := FALSE;
   Warning := FALSE;
END_IF;

CASE:

CASE State OF
   0: Motor := FALSE;
   1: Motor := TRUE;
   2: Motor := FALSE;
      Alarm := TRUE;
END_CASE;

FOR:

FOR i := 0 TO 9 DO
   Values[i] := 0;
END_FOR;

WHILE:

WHILE Buffer <> 0 DO
   Count := Count + 1;
   Buffer := Buffer / 2;
END_WHILE;

How ST Differs from General-Purpose Languages

Structured Text was designed for real-time control, which leads to some differences compared to languages like Python or C:

  • No dynamic memory allocation. All variables are declared at the top of a block and exist for the lifetime of the program. There is no malloc, new, or garbage collector.

  • No recursion. Function calls cannot recurse. This keeps execution time predictable.

  • Cyclic execution. Your program runs repeatedly as part of the scan cycle (see What is IEC 61131-3?). You do not write a main function that runs once — you write logic that runs every scan.

  • Time literals. Durations are first-class values: T#100ms, T#2s, T#1h30m.

These constraints exist because PLCs must respond within strict time deadlines. Predictability matters more than flexibility.

Next Steps

Now that you have a feel for the language, try writing your first program in the Quick start tutorial. When you need precise details about syntax and semantics, consult the Compiler reference.