P4080¶
- Code
P4080
- Message
Program instance type is not a declared PROGRAM
This error occurs when compiling a CONFIGURATION with a program instance
whose type is not a PROGRAM declaration, such as a function block or a
name that no file declares. A program instance runs the body of the
PROGRAM it names, so there is nothing to run.
Checking the configuration does not report this error, because a configuration is often kept in a file of its own and checked without the files that declare its programs. Compiling needs every program the configuration runs.
Example¶
The following code will generate error P4080:
FUNCTION_BLOCK Counter
VAR
n : INT;
END_VAR
n := n + 1;
END_FUNCTION_BLOCK
CONFIGURATION config
RESOURCE resource1 ON PLC
TASK task1(INTERVAL := T#10ms, PRIORITY := 1);
PROGRAM instance1 WITH task1 : Counter;
END_RESOURCE
END_CONFIGURATION
To fix this error, instantiate a PROGRAM, and call the function block from
it:
FUNCTION_BLOCK Counter
VAR
n : INT;
END_VAR
n := n + 1;
END_FUNCTION_BLOCK
PROGRAM main
VAR
counter1 : Counter;
END_VAR
counter1();
END_PROGRAM
CONFIGURATION config
RESOURCE resource1 ON PLC
TASK task1(INTERVAL := T#10ms, PRIORITY := 1);
PROGRAM instance1 WITH task1 : main;
END_RESOURCE
END_CONFIGURATION
When the program is declared in another file, compile that file together with the configuration.