P4099¶
- Code
P4099
- Message
PERSISTENT variable is declared by a function
This error occurs when a function declares a PERSISTENT or
RETAIN PERSISTENT variable.
A PERSISTENT variable keeps its value through a download, a reset and a
power cycle, so it needs storage that lasts from one call to the next. A
function keeps no values between calls, so it has nowhere to keep a
persistent value. TwinCAT also rejects PERSISTENT on a function’s
inputs.
Example¶
The following code will generate error P4099:
FUNCTION Twice : DINT
VAR_INPUT PERSISTENT
value : DINT;
END_VAR
Twice := value * 2;
END_FUNCTION
The function Twice declares the persistent input value, but a
function keeps no values between calls.
To fix this error, remove PERSISTENT from the function’s block, or move
the variable to a function block, whose instance keeps its values:
FUNCTION_BLOCK Twice
VAR_INPUT PERSISTENT
value : DINT;
END_VAR
VAR_OUTPUT
result : DINT;
END_VAR
result := value * 2;
END_FUNCTION_BLOCK
Think IronPLC is wrong about this?
If you believe this diagnostic is incorrect, open an issue on GitHub with a small sample that demonstrates the problem.