P4101¶
- Code
P4101
- Message
CASE label is not a value of the selector type
This error occurs when a CASE statement selects on an integer and one of
its labels is a name, such as an enumerated value.
A CASE compares the selector with each label, so each label must be a
value of the selector’s type. When the selector is an integer (INT,
DINT, a subrange of an integer type, or an integer literal), its labels
are integers and integer ranges. An enumerated value such as Fill is a
value of its enumeration, not an integer. A name that nothing declares is not
a value of any type.
Example¶
The following code will generate error P4101 twice:
TYPE
Mode : (Idle, Fill);
END_TYPE
PROGRAM main
VAR
step : INT;
alarm : BOOL;
END_VAR
CASE step OF
Fill: alarm := TRUE; (* Error: Fill is a Mode, not an INT *)
Drain: alarm := FALSE; (* Error: nothing declares Drain *)
END_CASE;
END_PROGRAM
step is an INT, so the labels of a CASE that selects on it are
integers. Fill is a value of Mode, and Drain is not declared.
To fix this error, label an integer selector with integers. Where the labels are the values of an enumeration, select on a variable of that enumeration:
TYPE
Mode : (Idle, Fill);
END_TYPE
PROGRAM main
VAR
step : INT;
mode : Mode;
alarm : BOOL;
END_VAR
CASE step OF
1: alarm := TRUE;
2: alarm := FALSE;
END_CASE;
CASE mode OF
Fill: alarm := TRUE;
Idle: alarm := FALSE;
END_CASE;
END_PROGRAM
See Also¶
CASE — the
CASEstatementP2006 — a label of a
CASEon an enumeration is not one of its valuesP2045 — a label is written with an enumeration other than the selector’s type
P4053 — the selector is not an integer or an enumeration
Think IronPLC is wrong about this?