P4092¶
- Code
P4092
- Message
R_EDGE or F_EDGE input is declared by a function or method
This error occurs when a function, a method or a property accessor declares
an R_EDGE or F_EDGE input.
An edge input is TRUE for the one call at which its value changes from
FALSE to TRUE (R_EDGE) or from TRUE to FALSE
(F_EDGE). Detecting the change means comparing the value with the one the
input had at the previous call, so the input needs memory that lasts from one
call to the next. A function block instance keeps its variables between calls;
a function, a method and a property accessor do not, so an edge input of theirs
has no previous value to compare with. Every dialect reports it.
Example¶
The following code will generate error P4092:
FUNCTION Pressed : BOOL
VAR_INPUT
button : BOOL R_EDGE;
END_VAR
Pressed := button;
END_FUNCTION
The function Pressed declares the edge input button, but a function
does not remember the value button had at the previous call.
To fix this error, detect the edge in a function block, whose instance keeps the previous value:
FUNCTION_BLOCK Pressed
VAR_INPUT
button : BOOL R_EDGE;
END_VAR
VAR_OUTPUT
pressed : BOOL;
END_VAR
pressed := button;
END_FUNCTION_BLOCK
The standard function blocks R_TRIG and F_TRIG detect an edge too,
and an instance of either can be called from any function block or program.